Certification
- tested in accordance with EN 1634-1
- classified according to EN 13501-2
- validated cycle test in accordance with C2 (> 10.000 cycles)
- CE marked in accordance with EN 13241 and EN 16034
Application
- only suitable for indoor / indoor situations
- only to be used in case of calamity (‘waiting’ function)
- mounting only possible on the wall / opening
- permissible mounting surfaces include: aerated concrete, sand-lime brick, concrete, masonry, fire-resistant steel construction, metal stud wall
Standard
- gravity failsafe tubular motor 230 V incl. control box
- optical / acoustic signaling
- galvanized steel side guides and cover box
Options include
- emergency battery (UPS) for maintaining open position in the event of a power failure
- galvanized steel parts powder coated in RAL color of choice
- visible parts side guides and cover box in stainless steel 304
- chamfered construction on top of cover box
- smoke detector for a stand-alone system
- various switches
classification |
fire resistance |
max. opening width |
max. opening height |
max. opening |
EW |
60 minutes |
8.000 mm |
8.000 mm |
48 m² |
EW |
90 minutes |
6.000 mm |
6.00 mm |
19,25 m² |
Due to continuous product development, we ask you to contact us for the current dimensions. Larger dimensions on request.